• 15 kV 630 A Shielded Separable Rear Surge Arrester Connector,Fengda Power,15 kV 630 A Shielded Separable Rear Surge Arrester Connector
  • 15 kV 630 A Shielded Separable Rear Surge Arrester Connector,Fengda Power,15 kV 630 A Shielded Separable Rear Surge Arrester Connector

15 kV 630 A Shielded Separable Rear Surge Arrester Connector

Download
View all downloads
  • 15 kV 630 A Shielded Separable Rear Surge Arrester Connector,Fengda Power,15 kV 630 A Shielded Separable Rear Surge Arrester Connector

Description

Technical Parameters

Main Technical Parameters Distribution Type Distribution Type Substation Type
Model SEBL0-12/36 SEBLQ-17/50 SEBLQ-17/45
Specification HY5WS-12/36 HY5WS-17/50 HYSWZ-17/45
Rated Voltage 12kV 17kV 17kV
System Nominal Voltage 10kV 10kV 10kV
Continuous Operating Voltage 9.6kV 13.6kV 13.6kV
Nominal Discharge Current 5kA 5kA 5kA
Lightning Impulse (8/20μs) ≤ 35.8kV 50kV 45kV
Switching Impulse (30/60μs) ≤ 30.6kV 42.5kV 38.3kV
Steep Front Impulse (1/10μs) ≤ 41.2kV 57.5kV 51.8kV
2ms Rectangular Wave Current ≥ 100A 100A 200A
DC Reference Voltage U1mA ≥ 19.0~20.0kV 26.0~27.0kV 25.0~25.9kV
High Current Impulse (4/10μs) ≥ 65kA 65kA 65kA
Leakage Current at 0.75U1mA ≤ 10μA 10μA 10μA

Note: 1. Products with parameters outside the table range can be customized upon user request after technical consultation with our engineering department.
           2.All product images and specifications displayed on our website are for reference only.Products may undergo routine upgrades to adapt to market demands, and website images & specifications cannot be updated
              synchronously in real time. There may be discrepancies between the images, specifications displayed online and actual delivered products.Accordingly, all specifications and dimensional standards shall be subject
              to the official product drawings provided by our technical team during technical consultation.