• 24 kV 630 A Shielded Separable Rear Surge Arrester Connector,Fengda Power,24 kV 630 A Shielded Separable Rear Surge Arrester Connector
  • 24 kV 630 A Shielded Separable Rear Surge Arrester Connector,Fengda Power,24 kV 630 A Shielded Separable Rear Surge Arrester Connector

24 kV 630 A Shielded Separable Rear Surge Arrester Connector

Download
View all downloads
  • 24 kV 630 A Shielded Separable Rear Surge Arrester Connector,Fengda Power,24 kV 630 A Shielded Separable Rear Surge Arrester Connector

Description

Technical Parameters

Parameter Name Class I Grounding Method - Substation Type Class I Grounding Method - Distribution Type Class II Grounding Method - Substation Type Class II Grounding Method - Distribution Type
Product Model SEBLQ-26/66 SEBLQ-26/72 SEBLQ-34/85 SEBLQ-34/90
Rated Voltage (r.m.s) 26kV 26kV 34kV 34kV
Continuous Operating Voltage (r.m.s) 20.8kV 20.8kV 27.2kV 27.2kV
DC Reference Voltage (U1mA) ≥37kV ≥37kV ≥48kV ≥48kV
Nominal Discharge Current (peak) 5kA 5kA 5kA 5kA
Switching Impulse Current (peak) 0.5kA 0.5kA 0.5kA 0.5kA
Power Frequency Reference Current (peak) 1mA 1mA 1mA 1mA
Power Frequency Reference Voltage ≥26kV ≥26kV ≥34kV ≥34kV
Residual Voltage under Lightning Impulse (5kA) ≤66kV ≤72kV ≤85kV ≤90kV
Residual Voltage under Switching Impulse Current ≤56kV ≤65kV ≤75kV ≤85kV
Residual Voltage under Steep Current Impulse ≤76kV ≤85kV ≤95kV ≤105kV
2ms Rectangular Wave Current Withstand 150A 150A 150A 150A
High Current Impulse Withstand Capability 65kA 65kA 65kA 65kA
Lightning Impulse Withstand Voltage of Shielded Connector Jacket 125kV 125kV 125kV 125kV
Power Frequency Withstand Voltage (r.m.s) of Shielded Connector Jacket 65kV 65kV 65kV 65kV

Note: 1. Products with parameters outside the table range can be customized upon user request after technical consultation with our engineering department.
           2.All product images and specifications displayed on our website are for reference only.Products may undergo routine upgrades to adapt to market demands, and website images & specifications cannot be updated
              synchronously in real time. There may be discrepancies between the images, specifications displayed online and actual delivered products.Accordingly, all specifications and dimensional standards shall be subject
              to the official product drawings provided by our technical team during technical consultation.