• LSY-10-107-Φ75 Three-in-one CT,Fengda Power,LSY-10-107-Φ75 Three-in-one CT
  • LSY-10-107-Φ75 Three-in-one CT,Fengda Power,LSY-10-107-Φ75 Three-in-one CT

LSY-10-107-Φ75 Three-in-one CT

Indoor Cast Resin Three-in-one Current Transformer
Download
View all downloads
  • LSY-10-107-Φ75 Three-in-one CT,Fengda Power,LSY-10-107-Φ75 Three-in-one CT

Description

Technical Parameters

Rated current ratio, accuracy class and its corresponding rated burden are listed in the table below; the rated secondary current is 5 A or 1 A.

Type LSY-10-107-Φ75 LSY-10-107-Φ75
LSY-10-107-Φ75

Application Measuring Current Transformer Protective Current Transformer Measuring & Protection Current Transformer
Rated Current Ratio (A) Accuracy Class and Rated Burden (VA) Accuracy Class and Rated Burden (VA) Accuracy Class and Rated Burden (VA)
0.5 1 10P10 10P5 0.5 1 10P10 10P5
150/1 2.5 1 2.5 1 1.5
200/1 2.5 5 1.5 2.5 1.5 1.5
300/1 3.75 7.5 2.5 3.75 2.5 1 2.5
400/1 5 10 2.5 5 3.75 1.5 3
500/1 7.5 15 3.75 7.5 5 2 4
600/1 10 20 5 10 5 2.5 5
150/5 2.5 1 2.5 1 1.5
200/5 2.5 5 1.5 2.5 1.5 1.5
300/5 3.75 7.5 2.5 3.75 2.5 1 2.5
400/5 5 10 2.5 5 3.75 1.5 3
500/5 7.5 15 3.75 7.5 5 2 4
600/5 10 20 5 10 5 2.5 5

Note: 1. Products with parameters outside the table range can be customized upon user request after technical consultation with our engineering department.
           2.All product images and specifications displayed on our website are for reference only.Products may undergo routine upgrades to adapt to market demands, and website images & specifications cannot be updated
              synchronously in real time. There may be discrepancies between the images, specifications displayed online and actual delivered products.Accordingly, all specifications and dimensional standards shall be subject
              to the official product drawings provided by our technical team during technical consultation.